Layout of ACVPP-H pressure conrol pilot
Technical parameters
- Nominal pressure: 2.8MPa
- Applicable temperature:-50℃ ~+120°c
- Test pressure:4.2MPa
- Applicable medium: ammonia, fluorine, propane,etc.
Characteristics
- The Pilots ACVP-H are used as constant pressure regulators,mounted directly over main valves AM1 or AM3 but can be also mounted on a housing valve ACVH in a external line to control one ormore AM or RAK valves.
- The Pilots ACVP-H working in higher pressure with a,range of regulation of 4 Bars to 25 Bars.
- Turning the regulating spindle clockwise,increases the opening pressure of the pilot,( thus the condensating pressure and temperature),and they decrease when we turn the spindle anticlockwise
- ACVP-H pilot valve is used to keep AM main valve inlet pressure constant. It can also be used as a safety valve, for example, to prevent excessive pressure due to the presence of effusion.
- The screw must be replaced with stainless steel bolt when it is used at ambient temperature below -50 C.
Pilot type | Maximum working pressure(bar ) |
KV(m3/h) | Temperrature range (℃) |
Pressure range (bar ) |
ACVP-HP | 28 | 0.4 | -50/+120 | 4-25 |
Pilot seat | L | L1 | H | D | d1 | B |
ACVH | 70 | 50 | 35 | 23.5 | NPT3/8 | M24x1.5 |