Technical parameters
- Nominal pressure: 2.8MPa
- Applicable temperature:-50°℃ ~+120°c
- Test pressure: 4.2MPa
- Applicable medium: ammonia, fluorine, propane,etc.
Characteristics
- The Pilots ACVP-L are used as constant pressure regulators, mounted directly over main valves AM1 or AM3 but can be also mounted on a housing valve EC type,ACVH in a external line to control one or more AM or RAK valves.
- The Pilots ACVP-L&ACVP-M both working in lower pressure,but in different range of regulation:ACVP—L:0 Bars~10 Bars、ACVP-M:—0.65 Bars~7 Bars
- Turning the regulating spindle clockwise,increases the opening pressure of the pilot, ( thus the evaporating pressure and temperature),and they decrease when we turn the spindle anticlockwise
- The guide valve is used to keep the inlet pressure of AM main valve constant.The low-pressure ACVP-L should avoid vibration.
- When ACVP is installed on the ACVH seat, it can be used as either a separate constant pressure valve or a safety pressure valve.
Pilot type | Maximum working pressure(bar ) |
KV(m3/h) | Temperrature range (℃) |
Pressure range (bar ) |
ACVP-L | 17 | 0.4 | -50/+120 | 0-10 |
ACVP-M | 17 | 0.4 | -50/+120 | 0.65-7 |
Pilot seat | L | L1 | H | D | d1 | B |
ACVH | 70 | 50 | 35 | 23.5 | NPT3/8 | M24x1.5 |