• TJ-12

Layout of ACVPL pressure conrol pilot

Short Description:


Product Detail

Product Tags

Technical parameters

  • Nominal pressure: 2.8MPa
  • Applicable temperature:-50°℃ ~+120°c
  • Test pressure: 4.2MPa
  • Applicable medium: ammonia, fluorine, propane,etc.

ACVPL pressure conrol pilot 恒压导阀L

Characteristics

  • The Pilots ACVP-L are used as constant pressure regulators, mounted directly over main valves AM1 or AM3 but can be also mounted on a housing valve EC type,ACVH in a external line to control one or more AM or RAK valves.
  • The Pilots ACVP-L&ACVP-M both working in lower pressure,but in different range of regulation:ACVP—L:0 Bars~10 Bars、ACVP-M:—0.65 Bars~7 Bars
  • Turning the regulating spindle clockwise,increases the opening pressure of the pilot, ( thus the evaporating pressure and temperature),and they decrease when we turn the spindle anticlockwise
  • The guide valve is used to keep the inlet pressure of AM main valve constant.The low-pressure ACVP-L should avoid vibration.
  • When ACVP is installed on the ACVH seat, it can be used as either a separate constant pressure valve or a safety pressure valve.

ACVPL pressure conrol pilot 恒压导阀L-1

Pilot type Maximum working
pressure(bar )
KV(m3/h) Temperrature range
(℃)
Pressure range
(bar )
ACVP-L 17 0.4 -50/+120 0-10
ACVP-M 17 0.4 -50/+120 0.65-7

 

Pilot seat L L1 H D d1 B
ACVH 70 50 35 23.5 NPT3/8 M24x1.5

  • Previous:
  • Next: