AVERA Solenoid valve
Characteristics
- AEVRAis a direct or servo-operated solenoid valve used in liquid, aspiration or hot gas pipelines of refrigerants such as ammonia and fluorine.
- AEVRAT is an auiliary open servo solenoid vave, which can be used in liquid, aspiration or hot gas pipeline of refrgerant such as ammonia or fuorine.
- The special design of AEVRAT makes it open without pressure diference, soit is especill suitable fo situatons requing zero prssure ditferenc.AEVRAT has manual opening device.
Technical parameters
Type | Opening pressure difference when using standard coil | Medium temperature | Maximum working pressure | Applicable medium | KV Value m3/h | |||
Min | Max (medium is liquid) | |||||||
10w a.c. | 12w a.c. | 20w a.c. | ||||||
AEVRA10 | 0.05 | 21 | 25 | 18 | -40~+105 | <4.0 | Ammonia fluorine,etc | 1.5 |
AEVRAT10 | 0.00 | 14 | 21 | 16 | -40~+105 | <4.0 | Ammonia fluorine,etc | 1.5 |
AEVRA15 | 0.05 | 21 | 25 | 18 | -40~+105 | <4.0 | Ammonia fluorine,etc | 2.7 |
AEVRAT15 | 0.00 | 14 | 21 | 16 | -40~+105 | <4.0 | Ammonia fluorine,etc | 2.7 |
AEVRA20 | 0.05 | 21 | 25 | 13 | -40~+105 | <4.0 | Ammonia fluorine,etc | 4.5 |
AEVRAT20 | 0.05 | 14 | 21 | 13 | -40~+105 | <4.0 | Ammonia fluorine,etc | 4.5 |
AEVRA25 | 0.20 | 21 | 25 | 14 | -40~+105 | <4.0 | Ammonia fluorine,etc | 10.0 |
AEVRA32 | 0.20 | 21 | 25 | 14 | -40~+105 | <4.0 | Ammonia fluorine,etc | 16.0 |
AEVRA40 | 0.20 | 21 | 25 | 14 | -40~+105 | <4.0 | Ammonia fluorine,etc | 25.0 |
Type | Rating cooling capacity | ||||||||
Liquid | Return gas | Hot gas | |||||||
R717 | R22 | R134a | R717 | R22 | R134a | R717 | R22 | R134a | |
AEVRAT10 | 142 | 30.2 | 27.8 | 9.0 | 3.4 | 2.5 | 42.6 | 13.9 | 11.3 |
AEVRAT15 | 256 | 54.4 | 50.1 | 16.1 | 6.2 | 4.4 | 76.7 | 24.9 | 20.3 |
AEVRAT20 | 426 | 90.6 | 83.5 | 26.9 | 10.3 | 7.3 | 128 | 41.5 | 33.9 |
AEVRA25 | 947 | 201 | 186 | 59.7 | 22.8 | 16.3 | 248 | 92.3 | 75.3 |
AEVRA32 | 1515 | 322 | 297 | 95.5 | 36.5 | 26.1 | 454 | 148 | 120 |
AEVRA40 | 2368 | 503 | 464 | 259 | 57.0 | 40.8 | 710 | 231 | 188 |
The working conditions for measuring the rated refrigerating capacity of liquid pipe and return pipe are: evaporation temperature te=-10 ° C, liquid temperature in front of valve is 25 ° C, and valve differential pressure is △P=0.15bar. The working conditions for measuring the rated cooling capacity of hot gas pipe are: condensation temperature tc=-40 ° C, valve differential pressure is △P=0.8bar, hot gas temperature is 65 ° C, undercooling is △tsub=4k